A system modification during runtime is based on the provisions you have made in

your initial configuration for an expansion of your PLC hardware. Define suitable

CiR compatible elements that you can later replace step-by-step in RUN mode with

real objects (slaves and/or modules). You can then download such a modified

configuration to the CPU during runtime.

Procedure

The table below shows the procedures required for modification of the program

and of the configuration, as well as the corresponding system phase.

Step      Action                                                                            CPU mode              System status
  
1 Configuration of your current (real) system configuration         STOP                       Offline configuration

2 Defining CiR elements                                                              STOP                       Offline configuration

3 Configuration download                                                            STOP                       Commissioning

4 Conversion of CiR elements to real objects where

required.

System modifications are only possible on master

systems which contain a CiR object or on ET 200M

stations which are equipped with a CiR module.                         RUN                        Continuous operation

If required, execute several passes of the CiR sequence (step 4 of the table

above). You merely have to provide a sufficient number of slaves or adequate I/O

volume for all of your system expansions before you switch to continuous

operation.

0 comments:

Post a Comment

Labels

Actuator Sensor-interface Address Negative Edge Detection Address Positive Edge Detection ADDRESSING ANALOG INPUTS ANALOG OUTPUTS AND Logic Operation AS-i AS-i configuration Assign Authorizations Automation License Manager BASICS Bit Bit Configuration Bit Logic Instructions Block By-passing CiR CiR Modules CiR Objects communication COMPARISON Components Configuration Configuring Connections Conversion Converting Counter CP 343-2 P CP 443-5 Ext CPU CPU 412-1 CPU 412-2 DP CPU 412-2 PCI CPU 414-2 DP CPU 414-3 DP CPU 414-4 H CPU 416-2 DP CPU 416-2 PCI CPU 416-3 DP CPU 416F-2 CPU 417-4 CPU 417-4 H Data Block DI/DO MODULES Diagnosing Diagnosis DIGITAL INPUTS DIGITAL OUTPUTS Downloading DP master English Mnemonics ET 200M Exclusive OR Logic Operation Extended pulse timer fail-safe modules fault FBD Floating- Point Floating-Point Math FUNCTION MODULES German Mnemonics Hardware hmi Input Insert Binary Input install Instructions Integer Math INTERFACE MODULES Jump License License Keys Load Memory Master Control Relay Memory Areas Memory Reset Midline Output Modifying MODULES monitoring variables Move NEG Negate Binary Input Negative RLO Edge Detection Networks Off-delay timer On-delay timer Operating systems OR Logic Operation Output PID Control PLC POS position decoder Positive RLO Edge Detection PROFIBUS Program Control programm Programming Pulse timer RELAY OUTPUTS Remote Reset Output Reset_Set Flip Flop Retentive on-delay timer Rotate RS S5 File S7 Communications S7-300 S7-400 SAVE Save RLO to BR Memory SCADA Set Output Set_Reset Flip Flop Shift siemens SIMATIC SIMATIC Manager Slaves Software SR STATEMENT Status Bit STEP 7 stop mode Time Base Time Value Timer Timer Cell TRAINING MODULE Units Upgrading UPLOADING WinLC RTX Word Logic Work Memory XOR