Requirements for Reconfiguration

Note

You can either use channels not previously used or reconfigure previously used

channels.

The addresses of available modules are not to be changed via CiR.

Configuration Requirements

In order to reconfigure the system, a CiR object must exist in the respective

DP master system.

Hardware Requirements

Please refer to the About text in the "Hardware Catalog" window for information on

which ET 200M modules (signal modules and function modules) you can

reconfigure in CPU RUN mode.

The maximum number of modules you can reconfigure is 100.

Module Response During a Reconfiguration

During reconfiguration the input modules can respond in one of the three following

ways:

Channels not affected will continue to return the actual process value.

Channels not affected will return the process value which was valid prior to the

reconfiguration.

All channels will return the value "0" (applies to digital modules and FMs) or

W#16#7FFF (applies to analog modules).

Please refer to the technical data of the specific modules for information on their

response.

Output modules respond as follows during reconfiguration:

The respective channels output the initial value which was valid before the

parameter assignment.

0 comments:

Post a Comment

Labels

Actuator Sensor-interface Address Negative Edge Detection Address Positive Edge Detection ADDRESSING ANALOG INPUTS ANALOG OUTPUTS AND Logic Operation AS-i AS-i configuration Assign Authorizations Automation License Manager BASICS Bit Bit Configuration Bit Logic Instructions Block By-passing CiR CiR Modules CiR Objects communication COMPARISON Components Configuration Configuring Connections Conversion Converting Counter CP 343-2 P CP 443-5 Ext CPU CPU 412-1 CPU 412-2 DP CPU 412-2 PCI CPU 414-2 DP CPU 414-3 DP CPU 414-4 H CPU 416-2 DP CPU 416-2 PCI CPU 416-3 DP CPU 416F-2 CPU 417-4 CPU 417-4 H Data Block DI/DO MODULES Diagnosing Diagnosis DIGITAL INPUTS DIGITAL OUTPUTS Downloading DP master English Mnemonics ET 200M Exclusive OR Logic Operation Extended pulse timer fail-safe modules fault FBD Floating- Point Floating-Point Math FUNCTION MODULES German Mnemonics Hardware hmi Input Insert Binary Input install Instructions Integer Math INTERFACE MODULES Jump License License Keys Load Memory Master Control Relay Memory Areas Memory Reset Midline Output Modifying MODULES monitoring variables Move NEG Negate Binary Input Negative RLO Edge Detection Networks Off-delay timer On-delay timer Operating systems OR Logic Operation Output PID Control PLC POS position decoder Positive RLO Edge Detection PROFIBUS Program Control programm Programming Pulse timer RELAY OUTPUTS Remote Reset Output Reset_Set Flip Flop Retentive on-delay timer Rotate RS S5 File S7 Communications S7-300 S7-400 SAVE Save RLO to BR Memory SCADA Set Output Set_Reset Flip Flop Shift siemens SIMATIC SIMATIC Manager Slaves Software SR STATEMENT Status Bit STEP 7 stop mode Time Base Time Value Timer Timer Cell TRAINING MODULE Units Upgrading UPLOADING WinLC RTX Word Logic Work Memory XOR