Requirements for Reconfiguration
Note
You can either use channels not previously used or reconfigure previously used
channels.
The addresses of available modules are not to be changed via CiR.
Configuration Requirements
In order to reconfigure the system, a CiR object must exist in the respective
DP master system.
Hardware Requirements
Please refer to the About text in the "Hardware Catalog" window for information on
which ET 200M modules (signal modules and function modules) you can
reconfigure in CPU RUN mode.
The maximum number of modules you can reconfigure is 100.
Module Response During a Reconfiguration
During reconfiguration the input modules can respond in one of the three following
ways:
•
Channels not affected will continue to return the actual process value.
•
Channels not affected will return the process value which was valid prior to the
reconfiguration.
•
All channels will return the value "0" (applies to digital modules and FMs) or
W#16#7FFF (applies to analog modules).
Please refer to the technical data of the specific modules for information on their
response.
Output modules respond as follows during reconfiguration:
The respective channels output the initial value which was valid before the
parameter assignment.