CPU's


CPU312IFM

CPU313

CPU314IFM

CPU314
Mem Statement/Bytes
2K/6KB
4K/12KB
8K/24KB
16K/48KB
Memory Cards
-
512KB FEPROM
-
512KB FEPROM
Processing Time 1024 Statements
0.6 ms
0.6 ms
0.3 ms
0.3 ms
DI & DO Max
256
256
1024
1024
AI & AO Max
64
64
256
256
Rack Configuration
1-Tier
1-Tier
4-Tier
4-Tier
Expansion Modules Max
8
8
31
31
Bit Memories
1024
2048
2048
2048
Counters
32
32
64
64
Timers
64
64
72
128
MPI Interface
187.5 Kbit/s
Max 32 Nodes
Yes
Yes
Yes
Yes
Integrated functions+Interfaces
10DI/6DQ onboard. int. functions:Counters/Freq. Measuremensts
-
20DI/16DQ ,4AI,1AO onboard. int. functions:Counters/Freq. Measuremensts/Positioning PID Control
-



CPU's


CPU315

CPU315-2DP

CPU316-2DP

CPU318-2
Mem Statement/Bytes
16K/48KB
16K/48KB
42K/128KB
256KB
Memory Cards
512KB FEPROM
512KB FEPROM
4MB FEPROM
4MB FEPROM
Processing Time 1024 Statements
0.3 ms
0.3 ms
0.3 ms
0.1 ms
DI & DO Max
1024
2048
4096
16384
AI & AO Max
256
256
256
1024
Rack Configuration
4-Tier
4-Tier
4-Tier
4-Tier
Expansion Modules Max
32
32
32
32
Bit Memories
2048
2048
2048
8192
Counters
64
64
64
512
Timers
128
128
128
512
MPI Interface
187.5 Kbit/s
Max 32 Nodes
Yes
Yes
Yes
Upto 12Mbaud
Integrated functions+Interfaces
-
PROFIBUS-DP Master/Slave (64 DP stations,12Mbaud)

PROFIBUS-DP Master/Slave (64 DP stations,12Mbaud)
PROFIBUS-DP Master/Slave (125 DP stations,12Mbaud)

* 1 K statements correspond to approx. 3Kbytes of user memory.



THE DIFFERENT TYPES OF MODULES AVAILABLE ARE

1.     SIGNAL MODULES  -  FOR DIGITAL AND ANALOG SIGNALS


DIGITAL INPUTS


DIGITAL OUTPUTS
·         16 X 24 VDC
·         8 X 120 / 230 VAC
·         16 X 120 V AC
·         32 X 24 V DC

·         16 x 24 VDC ,0.5A
·         8 X 24 VDC ,2A
·         8 X 120 / 230 VAC, 2A
·         16 X 120 VAC, 1A
·         32 X 24 V DC, 0.5A


RELAY OUTPUTS


DI/DO MODULES
·         8 X Relay 30 VDC ,0.5A
·         8 X Relay 250 VAC ,3A
·         16 X Relay 30VDC,0.5A
·         16 X Relay 120VAC, 2.5A

·         8DI/8DO X 24VDC 0.5A



ANALOG INPUTS PARAMETERIZABLE


ANALOG OUTPUTS PARAMETERIZABLE
·         8 Analog Inputs/ 2 Analog Inputs
·         +/- 10V , +/- 50 mV, +/-1 V, +/-20 Ma, 4 to 20mA, Pt100, Thermocouple

·         4 Analog Outputs/ 2 Analog Outputs
·         +/-10V, +/-50mV, +/-1 V, +/-20 mV, 4 to 20 mA

 


2.     FUNCTION MODULES 
·         High Speed Counter Modules - Upto 100 KHz range
·         Positioning Modules - For position control, Stepper Motor Control, Cam Controllers

All function modules are enclosed and can be installed in any slot.

3.     COMMUNICATION PROCESSORS - FOR DATA EXCHANGE WITH PRINTERS,COMPUTERS, SIMATIC SYSTEMS
·         CP340 - Point to Point Communication for the serial link with RS232, 3964R and any ASCII protocol

4.     INTERFACE MODULES - FOR MULTI TIER CONFIGURATION
·         For Central Controller Expansion
·         For Expansion Unit Connection

5.     POWER SUPPLY MODULES - FOR 24 VDC LOAD CIRCUITS WITH DIFFERENT RATINGS.


MPI - MULTI POINT INTERFACE FOR COMMUNICATION

·         MPI  INTEGRATED IN CPU
·         DATA EXCHANGE RATE : 187.5 Kbits / s
·         SIMULTANEOUS COMMUNICATION  WITH PG/PC/OP(OPERATOR PANEL) AND FURTHER PLCS REQUIRING NO ADDITIONAL HARDWARE
·         UPTO 32 NODES CAN BE CONNECTED

Labels

Actuator Sensor-interface Address Negative Edge Detection Address Positive Edge Detection ADDRESSING ANALOG INPUTS ANALOG OUTPUTS AND Logic Operation AS-i AS-i configuration Assign Authorizations Automation License Manager BASICS Bit Bit Configuration Bit Logic Instructions Block By-passing CiR CiR Modules CiR Objects communication COMPARISON Components Configuration Configuring Connections Conversion Converting Counter CP 343-2 P CP 443-5 Ext CPU CPU 412-1 CPU 412-2 DP CPU 412-2 PCI CPU 414-2 DP CPU 414-3 DP CPU 414-4 H CPU 416-2 DP CPU 416-2 PCI CPU 416-3 DP CPU 416F-2 CPU 417-4 CPU 417-4 H Data Block DI/DO MODULES Diagnosing Diagnosis DIGITAL INPUTS DIGITAL OUTPUTS Downloading DP master English Mnemonics ET 200M Exclusive OR Logic Operation Extended pulse timer fail-safe modules fault FBD Floating- Point Floating-Point Math FUNCTION MODULES German Mnemonics Hardware hmi Input Insert Binary Input install Instructions Integer Math INTERFACE MODULES Jump License License Keys Load Memory Master Control Relay Memory Areas Memory Reset Midline Output Modifying MODULES monitoring variables Move NEG Negate Binary Input Negative RLO Edge Detection Networks Off-delay timer On-delay timer Operating systems OR Logic Operation Output PID Control PLC POS position decoder Positive RLO Edge Detection PROFIBUS Program Control programm Programming Pulse timer RELAY OUTPUTS Remote Reset Output Reset_Set Flip Flop Retentive on-delay timer Rotate RS S5 File S7 Communications S7-300 S7-400 SAVE Save RLO to BR Memory SCADA Set Output Set_Reset Flip Flop Shift siemens SIMATIC SIMATIC Manager Slaves Software SR STATEMENT Status Bit STEP 7 stop mode Time Base Time Value Timer Timer Cell TRAINING MODULE Units Upgrading UPLOADING WinLC RTX Word Logic Work Memory XOR